Remko PWW 5000 Bedienungsanleitung Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 12
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
9
Technical Data PWW 5402 / PWW 5602
2 steps 2 steps
Type 5402 5602
Speed U/min. 670 500 660 500
Electrical connection
Volt 3 x 400 3 x 400 3 x 400 3 x 400
Frequency
Hz 50 50 50 50
Power consumption
kW 0,16 0,095 0,35 0,21
Rated current
A 0,38 0,19 0,78 0,39
Air capacity
m³/h 3470 2500 5500 4200
Sound pressure level L
pA
1m
1)
dB(A) 57 50 60 53
Max. heat projection range m 4,0 2,9 4,6 3,4
Heating medium connection
inch R 1“ R 1“ R 1“ R 1“
Weight kg 39 39 46
Heating Medium t
L1
°C kW t
L2
°C kW t
L2
°C kW t
L2
°C kW t
L2
°C
50/40 °C
0 19,9 18 17,0 21 27,1 15 24,1 17
5 17,4 21 15,0 23 23,6 18 21,1 20
10 14,9 24 12,8 26 20,2 22 18,0 23
15 12,4 27 10,8 29 16,8 25 15,1 26
20 9,9 29 8,7 31 13,6 28 12,2 29
60/50 °C
0 25,4 23 21,6 26 34,7 19 30,9 22
5 22,9 26 19,7 29 31,1 23 27,8 25
10 20,4 29 17,5 32 27,6 26 24,8 28
15 17,8 32 23,2 34 23,9 29 21,6 31
20 15,2 34 13,0 37 20,5 32 18,4 34
70/50 °C
0 25,3 22 21,7 26 27,1 15 24,3 17
5 22,8 26 19,9 29 24,0 19 21,4 21
10 20,3 29 17,8 32 20,9 22 18,6 24
15 17,6 31 15,7 35 17,7 25 15,8 27
20 15,6 35 13,7 38 15,0 29 13,1 30
80/60 °C
0 30,6 27 26,2 32 41,7 23 37,2 27
5 28,1 30 24,4 35 38,3 27 34,2 30
10 25,7 34 22,4 38 34,8 30 31,1 33
15 23,2 37 20,2 41 31,4 34 28,0 36
20 20,7 40 18,1 43 28,1 37 25,1 39
90/70 °C
0 36,1 32 30,9 37 49,5 28 44,0 32
5 33,7 35 29,0 41 45,9 31 40,9 35
10 31,2 39 25,9 *44 42,4 34 37,9 38
15 28,7 42 24,8 *47 38,7 38 34,7 41
20 26,2 *45 22,7 *49 35,3 41 31,7 *44
46
1) Noise measurement DIN 45635 - 01 - KL 3
2) t
L1
= incoming air temperature, t
L2
= outgoing air temperature
* For outgoing air temperatures above 42 °C a very strong thermal lift can form. The penetration depth of the warm air stream becomes shorter,
the cold air in the area where people are working cannot be adequately permeated and mixed by the warm air.
Temperature layers from bottom to top are the result. Pockets of cold air form in the area where people are working near the ceiling
Excessive buildup of heat (heat loss).