Edition GB – W11REMKO CMF - DUOCMF 320 DUOInverter heat pumpPlanning Guide and Installation Manual Instructions for the Technician

Seite 2

REMKO CMF - DUODefrost by circulation reversalAt temperatures below about +5°C, humidity freezes in the evaporator (outdoor module) and an ice layer c

Seite 3 - Contents

The role of the indoor unit of the CMF 320 Duo Inverter Heat Pump is to convert the condensation heat supplied by the outdoor unit for use on the heat

Seite 4

REMKO CMF - DUOInstallation instructionsThe indoor unit must be connected to the two outdoor modules with refrigerant pipes of dimensions (outside dia

Seite 5

These instructions are to be observed when installing the entire system. The device should be delivered as near as possible to the site of installa

Seite 6

REMKO CMF - DUO The wall bracket is to be attached to the wall with the fasteners supplied and the indoor module hooked onto it. The wall must posse

Seite 7 - Decompression

WindThe site for the outdoor module must be selected so that machinery noise that occurs disturbs neither the residents nor the facility operator. Obs

Seite 8

REMKO CMF - DUOLegLegFoundationFoundationCondensate drainage-heatingCondensate drainage-heatingDrainage channelDrain pipeSoilSoilGravel layer for seep

Seite 9

Hydraulic connection We recommend installing a buffer storage unit as a hydraulic switch for hydraulically isolation of the heating circuit. Make a

Seite 10

REMKO CMF - DUOCorrosion protectionOxygen always plays a role if metal materials in a heating system corrode. pH values and the salt content also play

Seite 11 - Layout of the indoor unit

Electrical connection It is necessary to lay a power-supply cable both to the outdoor module and, separately, to the indoor module. Power to the in

Seite 13 - Liquid line

REMKO CMF - DUOElectrical connection - indoor module1. Fold down or remove the lower housing-cover (Fig. 1).2. Loosen the two screws that secure the

Seite 14

Electrical connection - outdoor module The side wall of the the unit is to be removed by means of loosening the screws in order to connect the main

Seite 15 - 

REMKO CMF - DUOTemperature sensors External sensor The number of sensors required can vary with the type of system. In the indoor module (F11), the

Seite 16

The outdoor- and the indoor modules are connected with two copper pipes of refrigerator quality having the dimensions “ and “ (REMKO special accesso

Seite 17 - Indoor unit

REMKO CMF - DUOMonitoring for leaks Connect the manometer to at least one Schrader valve on the shut-off valves of the outdoor module. The leak tes

Seite 18

Control panel Mode switch Position I: Normal operation This switch turns on the system. The heat pump and a possible 2nd heat source (6 kW E-heater

Seite 19 - Electrical connection

REMKO CMF - DUONotes for commissioning The commissioning and programming of the heat-pump manager may be carried out only by an installer authorized b

Seite 20 - Electrical connection

Setting instructions for indoor unit charge pump The indoor unit incorporates a high-efficiency circulation pump to act as a charge pump. This circulat

Seite 21

REMKO CMF - DUOHeat pump manager Multi-Talent Plus (heat flow meters)Display levelThe displays relevant to the heat flow meters are called up with the f

Seite 22

Troubleshooting and customer serviceThe unit has been manufactured using state-of-the-art production methods and tested several times to ensure its co

Seite 23 - 65-75 Nm

ContentsRead these operating instructions carefully before commissioning / using this device!These instructions are an integral part of the system an

Seite 24

REMKO CMF - DUODisplay Fault description/noteHeat-pump fault (E 54)Heat pump fault The flow monitor has tripped. A flow problem has occurr

Seite 25 - Control panel

In the event that the red control lamp lights up on the indoor module, then the fault is on the outdoor module. Two LEDs are visible after removing th

Seite 26 - OK

REMKO CMF - DUOOverview of faults and their possible causes for the indoor unit charge pumpIndicator light does not illuminateIndicator light lights u

Seite 27 - 8.3 Fernbedienung R100



Seite 28

REMKO CMF - DUOElectrical system layoutOutdoor unit AOutdoor unit BPlatine WP-Manager (Merlin I/O circuit board)(slow- acting)(slow-acting)(slow-actin

Seite 29

Connection diagram, terminal configurationL1L2L3NOutdoor unitsS1S2S3On-site sub-distributionconnection layout CMF 320 DuoObserve the technical require

Seite 30

REMKO CMF - DUOCircuit diagramsPlatine WP-Manager (Merlin I/O circuit board)Power plant- Disable/ enableCircuit diagram WP01 - DuoMode switchHand-OFF-

Seite 31

Circuit diagram (continued)Load pump Indoor unitCircuit diagram WP02- Duo Switching valve 2. heat sourceOPENCLOSEDSpecial accessorieselectro heatin

Seite 32 - ADAPT or Constant pressure

REMKO CMF - DUOCircuit diagram (continued)Circuit diagram WP03-DuoSpecial accessorieselectro heatingFlow monitor *) or Jumper **)Circuit board WP mana

Seite 33 - Unit dimensions

Circuit diagram (continued)Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP04 - DuoMF4 outlet for solar pump or circula-tion pump or so

Seite 34

REMKO CMF - DUOCarefully read the operating instruction before placing the equipment in service. It provides useful tips and information as well as

Seite 35

REMKO CMF - DUOCircuit diagram (continued)Circuit diagram WP05 - Duo3 kW switchPower supply for electric booster-heating400V/3~/50Hz6 kW switchEl

Seite 36

Circuit diagram (continued)Circuit diagram WP06 - Duo Enable 2Heat source(potential-free normally open ornormally closed switch)Enable co

Seite 37 - Circuit diagram (continued)

REMKO CMF - DUOCircuit diagram (continued) Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP07 - DuoPumpHK 1OPEN3-waymixerHK 23-wayswitc

Seite 38

Circuit diagram (continued)Platine WP-Manager (Merlin I/O circuit board)Circuit diagram WP08 - Duo Outdoor unit A / Outdoor unit BUndercooling temper

Seite 39

REMKO CMF - DUOTerminal block/legendTermi-nalConnection layout (low-voltage sensor)X3. EarthX3.1 CAN-Bus +X3.2 CAN-Bus -X3.3 CAN-Bus LX3.4 CAN-Bus HX

Seite 40

Diagramm Heizleistung W35_28kW0102030405060-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20Char

Seite 41 - Outdoor unit B

REMKO CMF - DUODiagramm Heizleistung W45_28kW05101520253035404550-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Seite 42

Diagramm Heizleistung W55_28kW0510152025303540-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20C

Seite 43

REMKO CMF - DUOQ(m³/h)0 1 2 3 4 5 6 7 8 9 10 11H(m)012345678910P1(W)0408012016012345Pump-characteristic curves, indoor module charging pumpSound press

Seite 44

Overall sound-power level for one of the outdoor modulesExcluded rangeOutput A-bewCursor: (A)Power=67.1 dBMiddle frequency (Hz)25 31,50 40 50 63 80 10

Seite 45 - Characteristic curves

Care and maintenanceRegular care and maintenance serves to ensure trouble-free operation and long service-life of the heat-pump system.Care The indoo

Seite 46

REMKO CMF - DUOClimatic region: -10°CExisting buildings with hot-water heating (share 18%)TypeCOPAnnual performance number with inlet/outlet tem-perat

Seite 47

Climatic region: -10°CExisting buildings with hot-water heating (share 18%)TypeCOPAnnual performance number with inlet/outlet tem-perature differentia

Seite 48

REMKO CMF - DUOSeries CMF 320 DuoFunction Heating or CoolingInverter technologyREMKO SuperTecSystem Split-Air/WaterHeat pump managerMultitalent or M

Seite 49

Exploded view outdoor moduleSpare parts listNo. Designation EDP-number1 Compressor 11200822 Laminated heat-exchanger 11200833 Four-way switching valve

Seite 50

REMKO CMF - DUODevice display for indoor module CMF 320We reserve the right to modify the dimensions and constructional design as part of the ongoing

Seite 51 - Climatic region: -16°C

Spare parts listParts and fittings, setWhen ordering spare parts, please state the computerised part no., device number and device type (see identificat

Seite 52

REMKO CMF - DUOREMKO GmbH & Co. KG...Signa-ture Product ManagerEC – Declaration of Conformity We do hereby

Seite 53 - Spare parts list

General termsDefrost At outdoor temperatures below 5°C it is possible that ice may form on the evaporators of air/water heat pumps. The removal of th

Seite 54

REMKO CMF - DUOCompressor (condenser) Unit designed for the mechanical conveyance and compression of gasses. Compression serves to significantly incre

Seite 56

REMKO CMF - DUOEconomical and environmentally-conscious heatingThe burning of fossil-based energy sources in order to generate power creates severe co

Seite 57 - General terms

ConsultingThanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputa

Seite 58

Evaporation LiquefyingCondensingDecompressionFunctional diagram heating inverter heat pumpHeating pump outdoor unitOutdoor areaHeat pump indoor unitIn

Seite 59

REMKO CMF - DUOLayoutBuilding type Specific heating output in W/m2Passive energy house 10Low-energy house built in 2002 40according to energy conserva

Seite 60 - REMKO INTERNATIONAL

Characteristics of REMKO inverter heat pumpsOutdoor air as a heat sourceAn air/water heat pump absorbs energy from the outdoor air as its heat source