Issue D – U10REMKO GPMGas Wall HeaterOperation · Technology · Spare parts

Seite 2

10REMKO GPMModulationThe gas wall heaters are units with flame modulation, whereby the widest range of outputs between the minimum and maximum settings

Seite 3 - Contents

11Room correctionThe use of the electronic temperature regulation ATR-6 is required for this function. In the following, a type of function is describ

Seite 4

12REMKO GPMInstructions for the userFault displaysA green and red LED are installed on the front of the unit.The illumination of the green LED means

Seite 5 - Unit layout

13UnlockingWith malfunction of the fan-assisted air heater, it can be manually unlocked directly on the unit. There is a reset button for this purpose

Seite 6

14REMKO GPMResetting the unitsThe malfunction (lock-out) of the unit is displayed by the appearance of a flashing triangle on the display of the electr

Seite 7 - HW080909

15Operation and programming of the electronic temperature regulation ATR-6Operating mode With normal operating conditions the following information ap

Seite 8

16REMKO GPMSetting the weekly timer Heating mode (HTG)With the key KM you arrive at page 1 of the menu. Now press key K1 (HTG) in order to select the

Seite 9 - Reset button GREEN LED

17Programming of the HTG programming timer.With the key KM and then button K4 (>>) you arrive at page 2 of themenu.With the key K1 (PROG) the pr

Seite 10

18REMKO GPMFrost protectionThis function always remains active when switching off through the operating unit.The fan-assisted heater switches on if th

Seite 11 - Modulationstemperatur

19Automatic operationThe ventilation phase can also be operated automatically, where a weekly time programming is set, as described for heating.For us

Seite 13 - Operation with electronic

20REMKO GPMBy pressing K1 (-), K2 (T1) or K3 (T2) the desired parameter that should be adjusted to the required time period is selected; the menu auto

Seite 14

21The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (no living space heating in private use) on

Seite 15

22REMKO GPMThe following instructions for installation and set-up of the unitsare intended exclusively for authorised technicians.All safety notes mus

Seite 16

23Pivoting wall installationThe instructions for installation of the pivoting brackets are included with the packaging.The use of pivoting brackets is

Seite 17

24REMKO GPMHanging from the ceilingFor hanging the units by means of eyebolts, the Mounting set for ceiling installation with horizontal air outlet is

Seite 18

25e.g. Gas fireplace type C:The combustion cycle is compact compared to the environment in which it is installed.The combustion air is fed from outside

Seite 19

26REMKO GPMType B23 horizontalL1 maximum duct length without endpiecesØ 80 Ø 100Model MetresGPM15 29GPM25 29GPM35 26GPM55 15GPM 75 18Type B23 vertical

Seite 20

27Type C13 horizontal / coaxialL1 + L2 maximum duct length without endpiecesØ 80 Ø 100Model MetresGPM15 10 + 10GPM25 10 + 10GPM35 10 + 10GPM55 4.5 + 4

Seite 21

28REMKO GPMElectrical connectionThe electrical connection of the unit may only be carried out by authorised technicians (electrical power company-appr

Seite 22 - 200 1000

29Gas connectionLEGEND1 = Electrical gas solenoid valve Main burner2 = Electrical gas solenoid valve Ignition burner3 = Pressure regulator4 = Ele

Seite 23

3ContentsMade by REMKOThese operating instructions should be read carefully prior to commissioning / operation of the equipment!These instructions are

Seite 24 - Hanging from the ceiling

30REMKO GPMCombustion analysisStart the burner and bring it up to "high output" after switching on the fan by holding the reset button on th

Seite 25

31If the value lies beyond the indicated range, make adjustments with the CO2 regulating screw at the Venturi tube.- When tightening, the gas flow rat

Seite 26

32REMKO GPMCountry Category Natural gas Pressure Liquid gas PressureATII2H3B/PG20 20 mbar G30/G31 50 mbarBE <70 kWI2E(S)B,I3PG20/G25 20/25 mbar G31

Seite 27

33Check electrodes for their positioning according to instructions (see figure). It is important that the monitoring electrode [IO] lies tangential to

Seite 28

34REMKO GPM7) Inspection of the ionisation currentCarry out the inspection with a tester that is capable of detecting microampere values with DC. -

Seite 29 - 1 2 3 4 5 6 7 8

35The values that can be seen and adjusted with the electronic temperature regulation are found in the column PARAM K.NOTEWhen replacing the control P

Seite 30

36REMKO GPMUnit without electronic temperature regulationWith replacement of the gas valve, the CO2 and, if applicable, the offset value must be adjus

Seite 31

37The on-site conversion of the gas type may only be carried out by authorised, qualified technicians.Prior to the conversion, the country-specific requ

Seite 32

38REMKO GPMPARAM KTSPFactory settingStandard Description1 A1 0 0 - 100 Minimum modulation value2 A2 0 0 - 100 Maximum modulation value3 A3 70 20 - 100

Seite 33 - Maintenance

39Parameter PARAM KFor access to the PARAM K parameter, press the key KM (Menu) for approximately 8-10 seconds.The display shows:INFO REG ERR >&

Seite 34

4REMKO GPMSafety notesThe units were subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can emana

Seite 35 - CR switch

40REMKO GPMFault-findingTroubleshootingJANEINJANEINJAJANEINNEINJAJaBETRIEB NORMALNEINSieheStörungs-ursachenGerätentriegelnGerätblockiertBlinktdieses

Seite 36

41Type of faultsERRnur mit Temperatur-regelungF8F6F4F3F2F1Brenner zündet nichtSicherheitsthermostat (STB)Brennergebläse defektFühler NTC1 oder

Seite 37

42REMKO GPM N L230V 50HzM1VA1VA2NLPENLPELEDNTCElectrical connection diagramLegend:ACF = Flame monitoring unitB1 = Ignition burner solenoid valve

Seite 38

43When ordering spare parts, please state the computerised part no., unit number and type (see identification plate)!Exploded view366541329121413 7 811

Seite 39

44REMKO GPM1621221819252928273132333424152320263017Venturi burnerWe reserve the right to modify the dimensions and constructional design as part of th

Seite 40

45Spare parts listNo. Designation GPM15 GPM25 GPM35 GPM55 GPM 751 Control PCB 1110440 1110441 1110442 1110443 11104442 F1 Fuse 4A 1110445 1110445 111

Seite 41 - Type of faults

46REMKO GPMUnit dimensionsSeries Dimensions Opening Suspended unit Gas supplyL B H V HB LB IM IS ID DM GAS GO GVGPM15 720 640 650 140 530 415 450 116

Seite 42

47Technical dataSeries GPM15 GPM25 GPM35 GPM55 GPM 75min. max. min. max. min. max. min. max. min. max.Nominal thermal loadkW 12.5 16.5 20.0 26.5 24.0

Seite 43 - Exploded view

REMKO ACROSS EUROPE… and in your area!Profit from our experience and adviceConsultancyIntensive training means our consultants are always up-to-date wi

Seite 44

5Unit layoutOperating rangeModular systems can be created with the GPM-series gas wall heaters.Modular systems consist of one or multiple fan-assisted

Seite 45 - Spare parts list

6REMKO GPMDescription of the unitDefinition of the equipmentPursuant to EU Directives, the equipment is defined as:"Gas fan-assisted air heater wit

Seite 46

7The advantages of the units lie in the modular mode of operation, meaning the heat output created and thus the gas flow (consumption of fuel) are chan

Seite 47 - Technical data

8REMKO GPMThe interruption of the current supply during burning operation is not permitted for the same reasons, because lack of a secondary ventilati

Seite 48 - REMKO ACROSS EUROPE

9Faults FxThe control PCB mounted in the units differentiates between 6 different faults:F1 - Fault at the flame monitoring unit from loss of the flame